Gas Operated Solenoid Valve Type SPML
SPML Gas Operated solenoid Valves are servo-operated main valves with screwed-on
pilot solenoid valves. SPML valves use an external pressure
source for opening (which means that no differential pressure
across the SPML valve is required). This makes the valve
especially suitable for low-pressure suction lines. The
valves can be used in all types of refrigeration systems:
Direct expansion, Pump recirculation, Natural circulation,
within their specified pressure and temperature ranges SPML
valves can be used for fluorinated refrigerants (R 22, R 134a,
R 404A, R 12, R 502, etc.) or ammonia (R 717). Especially
suitable for systems where low pressure drop is required SPML
remains open even though the pressure drop across the valve is
0 bar. SPML pilot-operated solenoid valves can be installed
in: Suction lines, Return lines (liquid/vapour), Pressure-equalising
lines, Bypass lines.
Gas operated Solenoid valve type SPMLX two-step on/off
SPMLX are 2-step servo-controlled main valves with screwed-on
pilot solenoid valves. SPMLX valves use an external pressure
source for opening (which means that no differential pressure
across the SPMLX valve is required). SPMLX are used in suction
lines for the opening against high differential pressure, e.g.
after hot gas defrost in large industrial refrigeration
systems with ammonia or fluorinated refrigerants. SPMLX opens
in two steps: Step one opens to approx. 10% of the capacity,
when the pilot solenoid valves are activated. Step two opens
automatically after the pressure differential across the valve
reaches approximately 1.5 bar. Replaces SPML with bypass
solenoid valve, 2 signals and one timer. Stabilizes working
conditions and eliminates pressure pulsations during opening
after defrosting Provides safety against pressure "shocks" as
the valve can only open fully when ∆p < 1.5 bar.
Features:
1) Simple and inexpensive installation.
2) Stabilizes working conditions and eliminates pressure pulsations during opening after defrosting.
3) Screw thread pilot valve fitting.
4) Only one signal required for both pilot solenoid valves.
5) Provides safety against pressure "shocks" as the valves can only open fully when differential pressure is less than 1.5 bar.
|